ON-LINE MONITORING AND ANALYSIS OF FAULTS
IN TRANSMISSION AND DISTRIBUTION LINES USING GSM TECHNIQUE
ABSTRACT
Increase in demand of electricity for entire applications in any country,
need to produce consistently with advanced protection system. Many special
protection systems are available based on volume of power distributed and often
the load changes without prediction required an advanced and special
communication based systems to control the electrical parameters of the
generation. Most of the existing systems are reliable on various applications
but not perfect for electrical applications. Electrical environment will have lots
of disturbance in nature, Due to natural disasters like storms, cyclones or
heavy rains transmission and distribution lines may lead to damage. The
electrical wire may cut and fall on ground, this leads to very harmful for
human beings and may become fatal. So, a rigid, reliable and robust
communications like GSM technology instead of many communication techniques
used earlier. This enhances speed of communication with distance independency.
This technology saves human life from this electrical danger by providing the
fault detection and automatically stops the electricity to the damaged line and
also conveys the message to the electricity board to clear the fault. An
Embedded based hardware design is developed and must acquire data from
electrical sensing system. A powerful GSM networking is designed to send data
from a network to other network. Any change in parameters of transmission is
sensed to protect the entire transmission and distribution.
Keywords: Global System For Mobile Communication (GSM),Special
Protection System (SPS), Embedded Systems
INTRODUCTION
With the growing population of India and its rising
electric power needs, the demands on the power grid continue to rise. This
demand necessitates additional grid reliability. Special protection systems
(SPS) are an example of a class of protection schemes that can benefit from the
use of communication to increase their accuracy and reliability. The job of an
SPS is to detect system faults and take corrective action. Faults can be
broadly classified into two main areas which have been designated “Active” and “Passive”.
Types of faults in three phase system is shown in fig-1.
Fig-1 Types of Fault in Three phase system.
(A) Phase-to-earth fault.
(B) Phase-to-phase fault.
(C) Phase-to-phase-to-earth fault.
(D) Three phase fault.
(E) Three phase-to-earth fault.
(F) Phase-to-pilot fault.
(G) Pilot-to-earth fault.
The “Active” fault is when actual current flows from one phase conductor to
another (phase to phase) or alternatively from one phase conductor to earth
(phase-to-earth). This type of fault can also be further classified into two subgroup,
namely the “solid” fault and the “incipient” fault. The solid fault occurs as a
result of an immediate complete breakdown of insulation. Passive faults are not
real faults in the true sense of the word but are rather conditions that are
stressing the system beyond its design capacity, so that ultimately active
faults will occur. Typical examples are: Overloading - leading to overheating
of insulation
(Deteriorating quality, reduced life and ultimate failure). Over voltage -
stressing the insulation beyond its limits.
FAULT CHARACTERISTICS WITH & WITHOUT FAULT CURRENT LIMITER:
Fig-2 shows the wave shape of a typical unlimited fault current [16] as
well as the influence on this wave shape if FCL devices with and without fault
current interruption capability are applied to the system. A distinction among the
different types of FCL is made between passive and active fault current
limiting measures. Passive measures make use of already initially high source
impedance both at normal and at fault conditions whereas active measures bring
about a fast increase of the source impedance at fault conditions only.
Fig-2. Typical fault current wave shape and characteristic
data
Traditional SPS or special devices works with preplanning on load shedding.
Many technologies were used in different periods like carrier power line
communication, Radio frequency based control system, and Supervisory control
and data acquiring systems, Distributed control systems and Internet based communications.
Each of the above has merits and demerits. This paper is based on Robust GSM
technology meets safety reliability and fastest in design. GSM is an open,
digital cellular technology used for transmitting mobile voice and data
services. It divides each 200 kHz channel into eight 25 kHz time-slots. GSM operates
in the 900MHz and 1.8GHz bands. It has an ability to carry 64 kbps to 120 Mbps
of data rates.
BACKGROUND AND LITERATURE REVIEW:
Many special protection systems are available based on volume of power
distributed and often the load changes without prediction required an advanced and
special communication based systems to control the electrical parameters of the
generation.
CONVENTIONAL METHODS:
1. 1 The conventional remote operating and monitoring system:
Fig.3: The conventional remote operating and monitoring
system
Fig.3 shows the example of a conventional remote operating and monitoring
system (agent technology is not applied). In this system, the protection relay
equipment serves as a server, the PC in an office serves as a client, and the
PC and relay equipment communicate by 1 to 1. We can perform and follows some
personal computer in an office; download of the voltage and current data stored
in the relay equipment when relay equipment is activated by some power failure;
checking and changing the setting values of the protection relay; detecting an
abnormal occurrence and the relay activation caused by power system faults. As
an excellent information terminal which can acquire the real time data from a
power system. It is important that the information in a relay can be easily
accessed from an office and of which mechanism for performing the function described
above is simple. Because of the reason described above, the remote operating
and monitoring system has expanded steadily. Thus, although the remote
operating and monitoring system has outstanding features, the PC and protection
relay equipment are connected with the relations of 1 to 1, and while operating
this system, it is necessary that the operator looks at the PC browser continually
all the time. Moreover, in order to acquire information from a numbers of relay
equipment, an operator must specify the address of each relay to access them in
turn, which is complicated and time consuming. Furthermore, in this system,
even when relays are connected within the same network, the relays cannot
communicate and cooperate with each other. That is to say, relay equipment works
only as a server providing data to PCs located in the remote office.
1.2 POWER LINE COMMUNICATION (PLC):
It offers the possibility to use the well-developed infrastructure of the
electrical energy distribution grid for data transmission. For the time being, there
is no harmonized international standard for broadband PLC. But IEEE started standardization
of PLC physical and MAC layer in June 2005. In Europe, broadband PLC is limited
to frequencies between 1 and 30 MHz, because of restrictions regarding electromagnetic
compatibility (EMC). Future communication systems are expected to use much
higher data rates as today’s wireless local area networks (WLANs). In this
paper, we study an approach to boost high data rate wireless communications by
using existing power lines in a flexible and cost-efficient way. In wireless
networks, spatial diversity and spatial multiplexing gains are achieved by
multiple antennas at the transmitter and at the receiver. Using cooperative
relaying strategies these gains are also possible for single-antenna nodes.
Spatial multiplexing is mandatory to achieve the high bandwidth efficiency that
is necessary for future Gigabit/s wireless Communication systems.
1.3 RADIO FREQUENCY (RF):
Radio frequency (RF) is a rate of oscillation in the range of about 3 kHz
to 300 GHz, which corresponds to the frequency of radio waves, and the
alternating currents which carry radio signals. Electric currents that
oscillate at radio frequencies have special properties not shared by direct
current or alternating current of lower frequencies. The energy in an RF
current can radiate off a conductor into space as electromagnetic waves (radio
waves); this is the basis of radio technology. RF current can easily ionize
air, creating a conductive path through it. One of the biggest disadvantages to
radio communication technology is the limited range of a radio signal.
PROPOSED METHODOLOGY:
The proposed methodology is based on Robust GSM technology meets safety
reliability and fastest in operation. It consists of a sensing system, signal
conditioning electronic circuits, advanced embedded hardware for middle level computing,
a powerful computer network for further transmission of data to various places.
The above said system can able to communicate with one grid and its subsequent
related actions. This system is an Advanced intelligent Electronic device
(AIED). The Whole system must be employed to make perfect grid control system.
The system design is shown fig 2. The Sub elements of proposed system are
• Sensing Transformers.
• Signal Conditioners.
• Embedded based electronic Hardware.
• GSM technology for Data transfer.
• Powerful software to generate control signal
Fig 4: Block diagram of robust communication based SPS
for power system
Control switchgear refers to the combination of circuit breakers, fuses and
other electrical disconnections to isolate electrical equipment.
The purpose of switchgear is to shut down or deenergize specific equipment,
which will then allow work to be carried out further down the line. It is shown
in Fig.4
Fig 5: Control switchgear
Signal conditioners are essential to improve received signals. Removing the
unwanted frequencies during amplification. It consumes very low current from
the source. It consists of voltage sensing, current sensing, Frequency sensing.
The voltage sensing will senses any changes in the input voltage and output of
the circuit is given to PIC. Shown in Fig 6.
Fig 6: Block Diagram of voltage sensing
Current Sensing will senses any changes in the input current converted in
to voltage and given to the PIC shown in Fig 7
Fig.7: Block Diagram of Current sensing
Frequency Sensing will sense any changes in the frequency is converted into
voltage and given to the ADC. Schmitt trigger is used to convert any waveform
in to square waveform. XOR gate is used to double the frequency Shown in Fig 8
Fig 8: Block Diagram of Frequency sensing.
Fig 9: PIC Block diagram
Design Features
Fig 9 shows the block diagram of PIC 16F877A. Individual
power supply for Analog and Digital circuits is required to avoid drift on
analog portion. Double regulated filtered reference source is needed to ensure
safest ADC operation. External clock source must be used which enables the user
to design the required speed. External CPU Synchronous circuit must be designed
in case of PC requirement. External RS-232 is used for data transmission. Power
Supply Unit to Embedded consist of step down transformer to reduce the voltage,
rectifier to convert AC to DC, filter to remove unwanted AC signal and voltage
regulator to avoid the incoming voltage fluctuation and Keeps the output voltage(5V)
as constant for embedded controller.
To perform the various operations and conversions required to switch,
control and monitor the devices a processor is needed. The processor may be a
microprocessor, micro controller or embedded controller. In this work an
embedded controller has been preferred because of its industrial advantages in
power electronics like built in ADC, RAM, ROM, ports, USART, DAC. And also the
speed of embedded controllers is more compared to other processors. The
embedded controller selected for this work is PIC16F877A due to its various features.
A Relay driver is an Electro-magnetic Switch which is useful for a low
voltage circuit. The relays used in this work are compact, self-contained devices,
which respond to abnormal conditions.
In personal computer, data transfer takes place serially. RS-232standard is
used for serial communication. PIC Micro controller is linked to PC through the
RS-232 port. The hardware design of the above system is shown Fig 10.
Fig. 10: Hardware Implementations of special protection
systems
Algorithm without GSM
Step1: Initializing the PIC values i.e analog and digital values
Step2: Get voltage, Temp, Freq from PIC
Step3: Analog values from PIC will be read and display in the system
Step4: Plot voltage, Temp, Freq values
Step 5: Press the switch either in Kit or System
Step 6: If it checks for switch1 is pressed or not if sw1 is pressed then
it is on otherwise it goes or switch2 conditions
Step7: Plot current values
Step8: It will check for overload condition, if it is overload and the
circuit is tripped and shows the corresponding message in the system
Step9: If it is exists then end otherwise it goes to the step2
Algorithm with GSM
Step1: Initializing the PIC values i.e analog and digital values
Step2: Initializing the corresponding components of the GSM settings
Step3: Get voltage, Temp, Freq from PIC
Step4: Analog values from PIC will be read and display in the system
Step5: Plot voltage, Temp, Freq values
Step 6: Press the switch either in Kit or System
Step 7: If it checks for switch1 is pressed or not if sw1 is pressed then
it is on otherwise it goes for switch2 conditions
Step8: Plot current values
Step9: It will check for overload condition, if it is overload and the
circuit is tripped and then send the corresponding message to the mobile through
the GSM
Step10: If it is exists then end otherwise it goes to the step2.
RESULTS
Fig 11: shows without GSM when the feeder1 is ON, in
green color and the corresponding values are displayed
Fig 12: shows with GSM when the feeder2 is ON, in the
green colour and the corresponding values are displayed.
Fig.13: shows the database results of
voltage, incoming current, frequency, kvA, light and temperature for every
second.
Fig 14: shows with GSM when the feeder2 is Tripped
; it shows in pink color and the message will be send to the mobile through the
GSM when feeder2 is over loaded.
CONCLUSIONS:
This paper shows that a GSM technique can be successfully
apply to the earlier developed communication based special protection systems
to increase its reliability during network interruptions. The GSM enhances
speed of communication with distance independentancy. A suitable authenticated
hardware is designed to meet the credibility of the networking. An Embedded
based hardware is designed to acquire data from electrical sensing system; it
sends from one network to other and change in parameters of transmission to be sensed
to protect the entire transmission and distribution. GSM enables bi-directional
communication as a message or data.
Visual Basic software is used as interpreter among various tools and systems.
REFERENCES
[1].Luis A. Oquendo Class, Kenneth M.Hopkinson,
Member, IEEE, Xiaoru Wang, Senior Member, IEEE,Todd R. Andel, and Ryan
W. Thomas “A Robust communication based –special protection systemize transactions
on power delivery, vol. 25, no. 3, july 2010.
[2]. Takay Shono Katsuhiko Sekiguchi, Tatsuji Tanaka
Member, IEEE, and Shigeki Katayama. A Remote Supervisory System for A Power
system Protection and Control Unit Applying Mobile Agent Technology.
[3].Using key performance indicators to manage power
system reliability,john vangroup,Schneider electric.
[4]. key performance indicators of a transmission system,
Omar H. Abdalla*, Masoud Awlad-Thani, Mohamed Al- Wardi,Khalfan Al- Qaidi, Saqar
Al-Farsi, Ibrahim Al-Balushi, and Saeed Al-Mahdhooriaman electricity transmission
company, sultanate of a oman.
[5]. K. Hopkinson, G. Roberts, X. Wang, and J. Thorp,
“Quality of service considerations in utility communication networks,” IEEE Trans.
Power
[6]. Kenneth Hopkinson, Member, IEEE, XiaoruWang,
Member, IEEE, Renan Giovanini, James Thorp, Life Fellow, IEEE,Kenneth
Birman, and Denis Coury, Member, IEEE EPOCHS: A Platform for Agent-Based
Electric Power and Communication Simulation Built From
Commercial Off-the-Shelf Components IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 21,
NO. 2, MAY 2006
[7]. Perz, M. “A Method of Analysis of Power Line Carrier
Problems of Three-Phase Lines.” IEEE Transactions, Paper No. 63-937. June
1963.
[8] M. Gebhardt, F. Weinmann, and K. Dostert, “Physical
and regulatory constraints for communication over the power supply grid,” IEEE
Commun. Mag., vol. 41, no. 5, May 2003.
[9] Proc. IEEE Special Issue on GigabitWireless, vol.
92, no. 2, Feb. 2004.
[10] N. Laneman, D. Tse, and G.Wornell, “Cooperative
diversity in wireless networks: Efficient protocols and outage behavior,” IEEE
Trans. Inf. Theory, vol. 50, pp. 3062–3080, Dec. 2004.
[11] A. Sendonaris, E. Erkip, and B. Aazhang, “User
cooperation diversity—Part I and II,” IEEE Trans. Commun., pp.
1927–1948, Nov. 2003.
[12] I. Hammerström, M. Kuhn, and A. Wittneben, “Cooperative
diversity by relay phase rotations in block fading environments,” in Proc.
IEEE Workshop Signal Process. Advances Wireless Commun., Jul. 2004, pp.
293–297.
[13] R. U. Nabar, O. Oyman, H. Bölcskei, and A. Paulraj,
“Capacity scaling laws in MIMO wireless networks,” in Proc. Allerton Conf.
Commun.,Control and Comp., Oct. 2003, pp. 378–389.
[14] A. Wittneben and B. Rankov, “Distributed antenna
systems and linear relaying for gigabit MIMO wireless,” in Proc. IEEE Veh.
Technol.Conf.-Fall, Los Angeles, CA, Sep. 2004, pp. 3624–3630.
[15] Solid State Electronic Fault Current Limiter to
Limit the Fault Current in Power System Vinod Gupta, U. C. Trivedi, N. J. Buch Electrical
Research & Development Association, Vadodara-390010,NPEC-2010.
[16] Fault current limiters – application, principles and
experience, CIGRE WG A3.16: H.Schmitt*, J. Amon, D. Braun, G. Damstra,
K.-H.Hartung, J. Jäger, J. Kida, K. Kunde, Q. Le, L.Martini,M. Steurer, Ch.
Umbricht, X. Waymel and C. Neumann.