THREE PHASE FAULT ANALYSIS WITH AUTO RESET FOR TEMPORARY FAULT AND TRIP FOR PERMANENT FAULT
ABSTRACT
This
paper to develop an automatic tripping mechanism for the three phase supply
system. The project output resets automatically after a brief interruption in
the event temporary fault while it remains in tripped condition in case of
permanent fault. The electrical substation which supply the power to the
consumers, have failures due to some faults which can be temporary or
permanent. These faults lead to substantial damage to the power system
equipment. In India it is common, The faults might be LG (Line to Ground), LL
(Line to Line), 3L (Three lines) in the supply systems and these faults in
three phase supply system can affect the power system. To overcome this problem
a system is built, which can sense these faults and automatically disconnects
the supply to avoid large scale damage to the control gears in the grid
sub-stations. This system is built using three single phase transformers which
are wired in star input and star output, and 3 transformers are connected in
delta connections, having input 220 volt and output at 12 volt. This concept
low voltage testing of fault conditions is followed as it is not advisable to
create on mains line. 555 timers are used for handling short duration and long
duration fault conditions. A set of switches are used to create the LL, LG and
3L fault in low voltage side, for activating the tripping mechanism. Short
duration fault returns the supply to the load immediately called as temporary
trip while long duration shall result in permanent trip. The concept in the
future can be extended to developing a mechanism to send message to the
authorities via SMS by interfacing a GSM modem.
Keywords—555
Timer, Voltage regulator (LM7805), Relays, Comparator, Transformer (230 V– 12V
AC)
INTRODUCTION
Various
studies have shown that anywhere from 70%, to as high as 90%, of faults on most
overhead lines are transient. A transient fault, such as an insulator
flashover, is a fault which is cleared by the immediate tripping of one or more
circuit breakers to isolate the fault, and which does not recur when the line
is re-energized. Faults tend to be less transient (near the 80% range) at
lower, distribution voltages and more transient (near the90% range) at higher,
sub transmission and transmission voltages.
Lightning
is the most common cause of transient faults, partially resulting from
insulator flashover from the high transient voltages induced by the lightning.
Other possible causes are swinging wires and temporary contact with foreign
objects. Thus, transient faults can be cleared by momentarily de-energizing the
line, in order to allow the fault to clear. Auto reclosing can then restore
service to the line.
The
remaining 10 - 30% of faults are semi-permanent or permanent in nature. A small
branch falling onto the line can cause a semi-permanent fault. In this case,
however, an immediate de-energizing of the line and subsequent auto reclosing
does not clear the fault. Instead, a coordinated time-delayed trip would allow
the branch to be burned away without damage to the system. Semi-permanent
faults of this type are likely to be most prevalent in highly wooded areas and
can be substantially controlled by aggressive line clearance programs.
Permanent
faults are those that will not clear upon tripping and reclosing. An example of
a permanent fault on an overhead line is a broken wire causing a phase to open,
or a broken pole causing the phases to short together. Faults on underground
cables should be considered permanent. Cable faults should be cleared without
auto reclosing and the damaged cable repaired before service is restored. There
may be exceptions to this, as in the case of circuits composed of both
underground cables and overhead lines.
Although
auto reclosing success rates vary from one company to another, it is clear that
the majority of faults can be successfully cleared by the proper use of
tripping and auto reclosing. This de-energizes the line long enough for the
fault source to pass and the fault arc to de-energize, then automatically
recloses the line to restore service. Thus, auto reclosing can significantly
reduce the outage time due to faults and provide a higher level of service
continuity to the customer. Furthermore, successful high-speed reclosing auto
reclosing on transmission circuits can be a major factor when attempting to
maintain system stability. For those faults that are permanent, auto reclosing
will reclose the circuit into a fault that has not been cleared, which may have
adverse affects on system stability (particularly at transmission levels).
VOLTAGE REGULATOR
The
LM78XX/LM78XXA series of three-terminal positive regulators are available in
the TO- 220/D-PAK package and with several fixed output voltages, making them
useful in a Wide range of applications. Each type employs internal current
limiting, thermal shutdown and safe operating area protection, making it
essentially indestructible. If adequate heat sinking is provided, they can
deliver over 1A output Current. Although designed primarily as fixed voltage
regulators, these devices can be used with external components to obtain
adjustable voltages and currents.
Fig1 (a) Block diagram of voltage regulator
Fig1 (b) Absolute Maximum Ratings
It
has some features:
•
Output Current up to 1A.
•
Output Voltages of 5, 6, 8, 9, 10, 12, 15, 18, 24V.
•
Thermal Overload Protection.
•
Short Circuit Protection.
•
Output Transistor Safe Operating Area Protection.
SCHEMATIC DIAGRAM
Fig2 (a) Block diagram
Fig2 (b) Proposed schematic diagram
WORKING PRINCIPLE:
The
project uses 6numbers step-down transformers for handling the entire circuit
under low voltage conditions of 12v only to test the 3 phase fault analysis.
The primaries of 3 transformers are connected to a 3 phase supply in star
configuration, while the secondary of the same is also connected in star
configuration. The other set of 3 transformers with its primary connected in
star to 3 phase have their secondary’s connected in delta configuration. The
outputs of all the 6 transformers are rectified and filtered individually and
are given to 6 relay coils. 6 push buttons, one each connected across the relay
coil is meant to create a fault condition either at star i.e. LL Fault or 3L
Fault. The NC contacts of all the relays are made parallel while all the common
points are grounded. The parallel connected point of NC are given to pin2
through a resistor R5 to a 555 timer i.e. wired in monostable mode. The output
of the same timer is connected to the reset pin 4 of another 555 timer wired in
astable mode. LED’S are connected at their output to indicate their status. The
output of the U3 555 timer from pin3 is given to an Op-amp LM358 through wire
11 and d12 to the non inverting input pin3, while the inverting input is kept
at a fixed voltage by a potential divider RV2. The voltage at pin2 coming from
the potential divider is so held that it is higher than the pin3 of the Op-amp
used as a comparator so that pin1 develops zero logic that fails to operate the
relay through the driver transistor Q1.
This
relay Q1 is ‘3CO’ relay i.e. is meant for disconnecting the load to indicate
fault conditions.
OPERATING PROCEDURE:
While
the board is powered from a 3phase supply all the 6 relay coils get DC voltage
and their common point disconnects from the NC and moves on to the NO points
there by providing logic high at pin2 of 555 timer U1 i.e. that is kept on
monostable mode. While any push button across the relay is pressed it
disconnects that relay and in the process in common contacts moves to the NC
position to provide a logic low at trigger pin of 555 timer to develop an
output that brings the U3 555 timer which is used in astable mode for its reset
pin to high such that the astable operation takes place at its output which is
also indicated by flashing D11 LED.
If
the fault is off temporary in nature i.e. if the push button pressed is
released immediately the U1 monostable disables U3 the output of which goes to
zero in the event of any push button kept pressed for a longer duration the
monostable output provides a longer duration active situation for U3 the
astable timer the output of which charges capacitor C13 through R11 such that
the output of the comparator goes high that drives the relay to switch off
three phase load.
The
output of Op-amp remains high indefinitely through a positive feedback provided
for its pin1 to pin3 through a forward biased diode and a resistor in series.
This results in the relay permanently switched on to disconnect the load
connected at its NC contacts permanently off. In order to maintain the flow of
DC supply the star connected secondary set DC’S are paralleled through D8, D9
& D10 for uninterrupted supply to the circuit voltage of 12v DC and 5v DC
derived out of voltage regulator IC 7805.
HARDWARE TESTING
1.
Conductivity Test:
In electronics,
a continuity test is the checking of an electric circuit to see if current
flows (that it is in fact a complete circuit). A continuity test is performed
by placing a small voltage (wired in series with an LED or noise-producing
component such as a piezoelectric speaker) across the chosen path. If electron
flow is inhibited by broken conductors, damaged components, or excessive
resistance, the circuit is "open".
Devices
that can be used to perform continuity tests include multi meters which measure
current and specialized continuity testers which are cheaper, more basic
devices, generally with a simple light bulb that lights up when current flows.
An
important application is the continuity test of a bundle of wires so as to find
the two ends belonging to a particular one of these wires; there will be a
negligible resistance between the "right" ends, and only between the
"right" ends.
This
test is the performed just after the hardware soldering and configuration has
been completed. This test aims at finding any electrical open paths in the
circuit after the soldering. Many a times, the electrical continuity in the
circuit is lost due to improper soldering, wrong and rough handling of the PCB,
improper usage of the soldering iron, component failures and presence of bugs
in the circuit diagram. We use a multi meter to perform this test. We keep the
multi meter in buzzer mode and connect the ground terminal of the multi meter
to the ground. We connect both the terminals across the path that needs to be
checked. If there is continuation then you will hear the beep sound.
2.
Power ON Test:
This
test is performed to check whether the voltage at different terminals is
according to the requirement or not. We take a multi meter and put it in
voltage mode. Remember that this test is performed without ICs. Firstly, if we
are using a transformer we check the output of the transformer; whether we get
the required 12V AC voltage (depends on the transformer used in for the
circuit). If we use a battery then we check if the battery is fully charged or
not according to the specified voltage of the battery by using multimeter.
Then
we apply this voltage to the power supply circuit. Note that we do this test
without ICs because if there is any excessive voltage, this may lead to
damaging the ICs. If a circuit consists of voltage regulator then we check for
the input to the voltage regulator (like 7805, 7809, 7815, 7915 etc) i.e., are
we getting an input of 12V and a required output depending on the regulator
used in the circuit.
EX:
if we are using 7805 we get output of 5V and if using 7809 we get 9V at output
pin and so on.
This
output from the voltage regulator is given to the power supply pin of specific
ICs. Hence we check for the voltage level at those pins whether we are getting
required voltage. Similarly, we check for the other terminals for the required
voltage. In this way we can assure that the voltage at all the terminals is as
per the requirement.
RESULTS
fig 3.Practical Circuit of Linear load
Fig:4. Input voltage of Linear load
Fig.5.Practical Circuit of Non linear load
Fig.6.Input Voltage of Non linear load
Fig.7.Output voltage of the 12v dc supply (monostable)
Fig.8.Output voltage of the 12v dc supply(astable)
CALCULATIONS IN THERIOTICALLY:
For
L-G:
Pbase=500
mva, vbase=230
CONCLUSION
This
project is designed in the form of Hardware for three single phase transformers
230v to 12V of output for to develop an automatic tripping mechanism for
the three phase supply system while temporary fault and permanent fault
occurs. Here we used 555 timer with relay for the fault is temporary or
permanent.
Short
duration fault returns the supply to the load immediately called as temporary
trip while long duration shall result in permanent trip. The concept in the
future can be extended to developing a mechanism to send message to the
authorities via SMS by interfacing a GSM modem.
REFERENCES
[1]
Kimbark, Edward Wilson, ScD; Power System Stability; John Wiley & Sons,
Inc., N.Y., London
[2]
HAVRAN, F.J. 1999. Fault investigation on power transmission system.
ESKOM. Internaldocument: 38, 96-99KELLER, P. 1998. Correct fault analysis.
Eskom internal document
[3]
Turan Gonen, “Electric Power Transmission System Engineering, Analysis and
Design”, Crc Press Taylor and Francis Group.
[4]
Paul M. Anderson, “Analysis of Faulted Power Systems”, The Institute of Electrical
and Electronics Engineers, Inc., 1995. [
[5]
Miroslav D. Markovic, “Fault Analysis in Power Systems by Using the Fortescue
Method”, TESLA Institute, 2009.
[6]
Jun Zhu. “Analysis Of Transmission System Faults the Phase Domain”, Texas
A&M University. Master Thesis, 2004.
[7]
D. C. Yu, D. Chen, S. Ramasamy and D. G. Flinn, “A Windows Based Graphical
Package for Symmetrical Components Analysis”, IEEE Transactions on Power
Systems, Vol. 10, No. 4, pp 1742-1749, November 1995.
No comments:
Post a Comment